What this calculator does
This page converts a room’s air changes per hour to airflow in CFM, and the reverse. Fill length, width and height (or a volume), then type ACH or CFM; the other quantity solves. The identity is CFM = ACH × volume / 60.
Bathroom 50/20 CFM, whole-house 62.2, occupancy 62.1, kitchen hoods, ducts, coils and hydronic GPM are separate tools. Fire/smoke and health-care ventilation follow those specifications, not this room box.
How to use it
Enter dimensions and either ACH or CFM. Example loads a 12×14×8 ft room at 6 ACH (134.4 CFM). Open a card below when the job is a hood, a duct, a coil or water flow.
Unit chips switch feet/metres and CFM, m³/h or L/s. Related tools reuse the last airflow and temperatures you typed on this device.
Formula, units, and limits
CFM = ACH × L × W × H / 60 with feet and minutes. In SI, Q in m³/h = ACH × V with metres, because ACH is already per hour.
Inch-pound identities (CFM, ft, in. w.g., BTU/h, GPM) are the US HVAC default. SI chips use m³/h or L/s, metres, Pa, kW and L/s. 1 CFM ≈ 1.699 m³/h ≈ 0.472 L/s. 1 in. w.g. ≈ 249 Pa. Air density 0.075 lb/ft³ and the 1.08 / 0.68 / 500 / 24 factors assume near-standard air or water unless you override them.
When you would use it
Use this when you have a box and an air-change target. Use bathroom-fan or kitchen-hood when the talk is an exhaust table. Use whole-house for 62.2 and outdoor-air for 62.1.
None of these sketches replace a licensed mechanical engineer, a Manual J/D/S, a listed-hood submittal, or the mechanical code adopted on the job. Cleanrooms, health-care, and fire/smoke exhaust need those specifications.
Worked example
12 × 14 × 8 ft → 1344 ft³. At 6 ACH: 6 × 1344 / 60 = 134.4 CFM (about 228 m³/h).
The same box at 0.35 ACH is only 7.8 CFM. That is why dwelling ventilation and a bath fan are different pages.
FAQ
Is 6 ACH a code value?
No. It is the example. Offices, baths, tents and cleanrooms use different ranges. Open the room-ACH chart, then come back.
Does this size a bath fan?
Only as a volume check. Intermittent 50 CFM and continuous 20 CFM live on the bathroom-fan page.
Can I enter metres?
Yes. Switch the SI chips; the algebra is the same.
Does ACH here include infiltration?
No. This is mechanical air changes of the typed volume. ACH50 is a separate infiltration sketch.
Where do I go next?
Take the CFM to duct size, a hood, makeup air, or 62.1/62.2 if that is the job.
Is this a load calculation?
No. Sensible heat 1.08 and tons are in the heat group. This page is volume and air changes only.
References
- ASHRAE Standard 62.1 and 62.2 — outdoor-air and dwelling-ventilation forms (overview of published identities; tables remain in the licensed standard).
- International Mechanical Code — residential bath/kitchen exhaust discussion values commonly implemented as 50/20 CFM; confirm the adopted year.
- ASHRAE Fundamentals — moist-air relations, duct fitting concepts, fan laws, hydronic constants 500 and 1.08.
- ISO 14644-1 — cleanroom classification names (particle limits, not a mandatory ACH).
- Magnus / WMO saturation vapor-pressure approximations for dew point.
- Huebscher equivalent-diameter relation for rectangular ducts.
Disclaimer
A room ACH sketch is not a permit, a Manual J, or a listed-hood rating.
Results are estimates computed on your device. Nameplate curves, TAB measurements, and the authority having jurisdiction control the installation. This site does not size combustion air, refrigerant charge, fire dampers, medical gas, or electrical conductors.